Electro-hydrodynamic (EHD) enhancement of external condensation of refrigerant R-134a for a seven-tube bundle heat exchanger was studied experimentally. The tubes used in the bundle were commercially available, state of the art enhanced tubes provided by a heat transfer tube manufacturer. Both horizontal and vertical bundle configurations were tested at different heat flux levels, ranging from 10 to 30 kW/m2. The saturation temperature was 30 °C and the applied electric field voltage ranged from 0 to 20 kV. The results obtained indicated that the external heat transfer coefficients increased with increase in the applied electric field, and that EHD had a more significant influence for the vertical bundle orientation. A maximum of nearly fourfold enhancement was achieved for the vertical configuration, compared to a maximum enhancement of 38% for the horizontal configuration. The EHD technique is accordingly more efficient for heat transfer augmentation in vertical condenser orientations where the base line (non EHD enhanced) heat transfer are rather poor.
Skip Nav Destination
ASME 2003 International Mechanical Engineering Congress and Exposition
November 15–21, 2003
Washington, DC, USA
Conference Sponsors:
- Heat Transfer Division
ISBN:
0-7918-3718-1
PROCEEDINGS PAPER
Electrohydrodynamically (EHD) Augmented External Condensation for R-134a in a Tube Bundle Heat Exchanger
M. M. Ohadi,
M. M. Ohadi
University of Maryland, College Park, MD
Search for other works by this author on:
S. Thorpe,
S. Thorpe
University of Maryland, College Park, MD
Search for other works by this author on:
J. Qi
J. Qi
University of Maryland, College Park, MD
Search for other works by this author on:
J. Wu
University of Maryland, College Park, MD
M. M. Ohadi
University of Maryland, College Park, MD
S. Thorpe
University of Maryland, College Park, MD
J. Qi
University of Maryland, College Park, MD
Paper No:
IMECE2003-42351, pp. 123-128; 6 pages
Published Online:
May 12, 2008
Citation
Wu, J, Ohadi, MM, Thorpe, S, & Qi, J. "Electrohydrodynamically (EHD) Augmented External Condensation for R-134a in a Tube Bundle Heat Exchanger." Proceedings of the ASME 2003 International Mechanical Engineering Congress and Exposition. Heat Transfer, Volume 4. Washington, DC, USA. November 15–21, 2003. pp. 123-128. ASME. https://doi.org/10.1115/IMECE2003-42351
Download citation file:
6
Views
0
Citations
Related Proceedings Papers
Related Articles
Augmentation of Thin Falling-Film Evaporation on Horizontal Tubes Using an Applied Electric Field
J. Heat Transfer (May,2000)
Falling Film and Spray Evaporation Enhancement Using an Applied Electric Field
J. Heat Transfer (November,2000)
Related Chapters
Techniques to Reduce Exchanger or System Cost
Heat Exchanger Engineering Techniques
Threshold Functions
Closed-Cycle Gas Turbines: Operating Experience and Future Potential
Thermal Design Guide of Liquid Cooled Systems
Thermal Design of Liquid Cooled Microelectronic Equipment