This paper focuses on validating a theoretical method for the detection of leaks in deep water, multi-phase pipelines. [1] Six field-scale, two-phase flow tests were conducted to compare small leaks with a no-leak condition. These tests qualitatively demonstrate the feasibility of Scott’s concept. Knowing the characteristic pressure loss versus throughput in a line without a leak provides a basis for determining the presence of a leak by measuring pressure loss and flowrate out of the line. If the pressure loss is higher than expected for that flowrate, a leak is a likely possible cause. In these full-scale tests, a leak was readily detectable once the leak rate exceeded 16 percent for the case where the average rate exiting the line was 547 MCFPD. These tests were performed on a 3.64 inch (9.25 cm) internal diameter 9,640 foot (2,938 m) long flow loop with the leak occurring at the midpoint.